ARK Engineering Solutions
CircuitCalc
Enclosure internal fit-out calculation report
Project
MCC-01 internal fit-out
Enclosure
ENCL-A
Issued
29 October 2026
Document
CC-ENCL-A
Design status
COMPLIANT
45 pass · 0 check · 0 fail
5 outgoing circuits
1. Supply and incomer
| System | AC 3φ 415 V 50 Hz |
| Incoming fault level | 25.0 kA |
| Earth fault (Ief) | Derived from Isc |
| Ambient | 40 °C |
| Design PF | 0.85 |
| Voltage-drop limit | 5.0 % |
| Grouping (default) | 2 circuits bunched |
| Incomer | MCCB 250 A · Icu 36 kA |
2. Main bus
| Construction | 50 × 6 mm Cu busbar |
| Length | 1.20 m |
| CSA | 300 mm² |
| Rating | 450 A |
| Σ Ib / diversified | 98.0 A / 78.4 A |
| Bus voltage drop | 0.01 % (0.02 V) |
| Isc at bus | 24.5 kA |
| Adiabatic Smin (0.1 s) | 49.7 mm² |
| Bus checks | COMPLIANT |
3. Outgoing circuit schedule
| Tag | Load | Ib | Device | CSA | PE | L | Iz | VD | Isc | Zs | Lmax | OK |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Q1 | Lighting — LED battensLighting | 12.0 A | MCB Type C 16 ARCD | 2.5 mm² | 2.5 mm² | 35.0 m | 17 A | 1.46 % | 0.69 kA | 0.691 Ωmax 1.498 | 120 m | Pass |
| Q2 | GPO circuit — workshopSocket / GPO | 12.0 A | MCB Type C 16 ARCD | 2.5 mm² | 2.5 mm² | 28.0 m | 17 A | 1.16 % | 0.85 kA | 0.555 Ωmax 1.498 | 120 m | Pass |
| Q3 | Pump motor DOLMotor | 42.0 A | MCB Type C 63 A | 16.0 mm² | 16.0 mm² | 45.0 m | 64 A | 0.97 % | 3.15 kA | 0.144 Ωmax 0.380 | 125 m | Pass |
| Q4 | VSD feeder — conveyorVSD / drive | 28.0 A | MCCB 32 A | 6.0 mm² | 6.0 mm² | 22.0 m | 38 A | 0.98 % | 2.34 kA | 0.197 Ωmax 0.749 | 88 m | Pass |
| Q5 | 24 V control / PLC (from 415 V)Control / PLC | 4.0 A | MCB Type C 10 A | 1.5 mm² | 1.5 mm² | 18.0 m | 12 A | 0.41 % | 0.80 kA | 0.594 Ωmax 2.396 | 74 m | Pass |
Installation: In wiring enclosure unless noted on the circuit. Conductor typically Cu. Lmax is the lesser of voltage-drop and earth-fault loop limits.
4. Protection and compliance checks
All applied AS/NZS 3000 and AS/NZS 3008 checks passed for the incomer, main bus and outgoing circuits as entered.
5. Basis of calculation
- Current-carrying capacity from AS/NZS 3008.1.1 typical Australian conditions (40 °C air unless a different ambient is entered). Ambient and grouping factors applied.
- Protection coordination: Ib ≤ In ≤ Iz (AS/NZS 3000 cl 2.5.3). Breaking capacity Icu ≥ prospective Isc (cl 2.5.4). Short-circuit withstand S ≥ I√t / k (AS/NZS 3008 Table 52).
- Voltage drop: 3φ √3 I L (R cosφ + X sinφ); 1φ and DC 2 I L R. Limit as entered (default 5 %, AS/NZS 3000 cl 3.6.2).
- Earth-fault loop: Zs = Ze + Zbus + (Zph + Zpe) × L. Zs max = U0 / Ia for 0.4 s disconnection. Earth CSA from Table 5.1 and the adiabatic equation.
Prepared by
Checked by
Date
29/10/2026